Compliance Guides

    Foam Concentrate Testing on Ships: MSC.1/Circ.1312 Intervals, Lab Tests and PFOS Records

    By Baltimore Marine Safety |

    The MSC.1/Circ.1312 rule of a first test within three years of supply and every year after, the five properties the lab checks against the batch certificate, how to take a 2 litre sample, and the PFOS declaration now expected since 1 January 2026.

    Navy graphic titled Foam Concentrate Testing on Ships, with icons for a first test within 3 years of supply, then every year, and a 2 L sample

    Foam concentrate on a ship does not stay good forever. Heat, contamination and a half-empty tank can age it faster than the date on the drum suggests, and you cannot see the problem by looking at it. That is why IMO MSC.1/Circ.1312 calls for periodic laboratory control of the concentrate stored on board: the first test not more than three years after the foam is supplied to the ship, and every year after that. Each test checks the same handful of properties against the values on the maker's batch certificate.

    Most of what comes up when you search for foam concentrate testing is written for shore tanks and fire sprinkler contractors. This guide is the shipboard version: which foam the circular covers, what the lab actually measures, how to take a sample from a ship's tank, what has changed since the PFOS ban took effect on 1 January 2026, and the records a class surveyor or Port State Control examiner will expect to see in Baltimore, Philadelphia, the Delaware River, New York and New Jersey, or Norfolk.

    Which foam MSC.1/Circ.1312 covers

    Circ.1312 is titled "Revised guidelines for the performance and testing criteria, and surveys of foam concentrates for fixed fire-extinguishing systems." Paragraph 1.1 applies it to the foam concentrates used in:

    • Fixed deck foam systems on tankers, under SOLAS regulation II-2/10.8 and chapter 14 of the Fire Safety Systems (FSS) Code.
    • Fixed deck foam systems on chemical tankers, under the IBC Code.
    • Fixed foam systems in machinery spaces, under chapter 6 of the FSS Code.
    • Portable foam applicators, under chapter 4 of the FSS Code.

    It covers the concentrate only. The circular states plainly that it does not apply to the foam generating equipment, so proportioners, foam makers, monitors and piping are inspected and tested under the vessel's maintenance plan, not under Circ.1312. Our MSC.1/Circ.1432 inspection schedule guide covers the system side.

    High-expansion foam concentrate has its own IMO guidelines, MSC/Circ.670, so check which circular your product was approved under before you send a sample.

    The test interval: three years, then every year

    Section 5 of the circular sets the timing: "the first periodical control of foam concentrates should be performed not more than 3 years after being supplied to the ship, and after that, every year." The clock starts when the concentrate is delivered to the ship, not when it was manufactured.

    That detail matters more than it looks. If nobody recorded when the current concentrate came aboard, there is no way to show when the first test was due, and the safest reading is that it is due now. The delivery date belongs in the foam records next to the batch certificate.

    There is one exception. Protein-based alcohol-resistant concentrates also need an acetone stability test, and that test is done before delivery to the ship and annually after that, with no three-year grace period.

    What the lab measures

    Section 4 lists the periodical controls. They are the same properties the maker declared when the concentrate was approved, so the lab is really answering one question: has this concentrate drifted away from what was delivered?

    TestWhat it tells youReference in Circ.1312
    SedimentationWhether insoluble particles have formed. At type approval the sediment must be no more than 0.25% by volume and must disperse through a 180 µm sieve.4.1 (method in 3.3)
    pH valueChemical change or contamination. At type approval the pH must be between 6 and 9.5 at 20 ± 2ºC.4.2 (method in 3.5)
    Expansion ratioHow much foam a given volume of solution makes, tested with simulated sea water.4.3 (method in 3.7)
    Drainage timeHow quickly the foam breaks down and releases its liquid (the 25% drainage time).4.4 (method in 3.8)
    Volumic mass (density)Dilution, contamination or the wrong product in the tank.4.5 (method in 3.11)
    Small scale fire testProtein-based alcohol-resistant concentrates only.4.6
    Chemical stability with acetoneProtein-based alcohol-resistant concentrates only. The concentrate fails if the foam solution mixes with the acetone.4.7

    Two details are worth knowing when you read a lab report. First, the sedimentation, expansion ratio and drainage tests are run on a sample held at 60ºC for 24 hours and then cooled, which is meant to show how the concentrate behaves after heat stress. Second, the circular does not set fixed pass marks for periodical controls. The results are compared with the values from type approval, and the deviations "should be within the ranges acceptable to the Administration." In practice that means the report is only as useful as the batch certificate it is compared against.

    The batch certificate is the baseline

    Paragraph 3.12 says foam concentrate "should be delivered with a declaration of the main characteristics (sedimentation, pH value, expansion ratio, drainage time and volumetric mass)," issued by the maker, and that this declaration "will be the basis for the annual condition test."

    If the batch certificate is not on board, the lab can still measure the sample, but nobody can say how far the results have moved from the delivered product. Keep the certificate with the foam records, and when concentrate is topped up or replaced, keep the certificate for the new batch too.

    Paragraph 3.13 lists what each foam container should be marked with, including the batch number and a reference to its batch certificate, the date of manufacture, the expiry date, the recommended usage concentration, whether it is seawater compatible, and the minimum and maximum storage temperatures. Those markings are the quickest way to confirm that the product in the tank is the product on the certificate.

    How to take a foam sample on board

    The circular asks for 2 litres for a periodical control and says the sampling method "should ensure representative samples which should be stored in filled containers." A few practical points follow from that:

    1. Take it from the concentrate the system will actually use. A sample from a spare pail in the store tells you about the pail, not the tank.
    2. Think about where in the tank it comes from. Sediment settles, so a sample drawn only from the top of a tall tank can look better than the concentrate near the outlet. Some shore labs ask for top and bottom samples from large tanks for the same reason. Follow the instructions of the lab or service supplier doing the test.
    3. Fill the container. A full bottle leaves little air in contact with the concentrate on its way to the lab.
    4. Label it fully. Vessel name, tank or system, product name, batch number, date sampled and date the concentrate was supplied to the ship.
    5. Send the batch certificate with it. The results mean little without the values they are compared against.

    Section 4 says these tests are the shipowner's or operator's responsibility and "should be carried out at laboratories or authorized service suppliers acceptable to the Administration." If you are not sure whether a lab is acceptable to your flag, ask the flag or class before the sample goes out, not after the report comes back.

    The PFOS ban: what changed on 1 January 2026

    Resolution MSC.532(107) amended SOLAS regulation II-2/10 to prohibit the use and storage of fire-extinguishing media containing perfluorooctane sulfonic acid (PFOS) on board. The amendment entered into force on 1 January 2026. Ships constructed on or after that date had to comply on delivery. Existing ships had to comply by their first survey on or after that date, meaning whichever annual, periodical or renewal survey for the safety equipment certificate (or the equivalent ship safety certificate) came first.

    The IMO unified interpretation of the new regulation, MSC.1/Circ.1694, fills in how it is checked:

    • "Containing PFOS" means PFOS present above 10 mg/kg (0.001% by weight).
    • The Administration or its recognized organization verifies compliance by reviewing the maker's declaration or laboratory test reports for the extinguishing media.
    • The maker's declaration should identify the foam, such as the foam type, production period, batch number and the reference to its type approval or MED certificate.
    • For media installed before 1 January 2026 with no maker's declaration or test report, sampling and testing on board should be required, to a recognized standard.

    The practical result is that the PFOS-free declaration is now part of the foam paperwork, alongside the batch certificate and the periodical test reports. ABS guidance adds that PFOS foam taken off a ship should go to an appropriate shore reception facility and recommends recording the removal in the official logbook. If the concentrate was replaced, the new product needs its own batch certificate and declaration, and its own three-year clock starts on the day it came aboard.

    Note what the ban does not do. The IMO considered widening it to all PFAS and decided against it for now, so a fluorinated foam that is not a PFOS foam is not prohibited by this amendment. Do not assume an older AFFF is compliant either. The declaration or test report is what shows it.

    Records to have ready for a survey or Port State Control

    • The batch certificate for every concentrate in the system and in the spares.
    • The date each batch was supplied to the ship.
    • The latest periodical control report, with the next one scheduled inside 12 months (or inside three years of delivery for a first test).
    • The maker's PFOS declaration or a laboratory test report showing the foam is PFOS-free.
    • For protein-based alcohol-resistant concentrate, the annual acetone stability result.
    • The maintenance plan entries for the foam system hardware: proportioner, foam makers, monitors and applicators.

    Common gaps in foam concentrate records

    • No delivery date. Without it, the three-year first test cannot be shown to be on time.
    • No batch certificate on board. The test report has nothing to be compared against.
    • Report for a different product. The tank was topped up with another concentrate after the last sample, so the report no longer describes what is in the tank. Check with the maker before mixing products in one tank at all.
    • Expired concentrate. The expiry date on the container marking has passed.
    • Storage that ages the foam. The circular itself warns that "excessive ambient storage temperature, contamination of the foam concentrate, incomplete filling of the tank" can cause abnormal ageing. A foam tank in a hot space, or one left partly empty, is worth testing on schedule rather than late.
    • No PFOS declaration. Since the first survey after 1 January 2026, a surveyor expects to see it.

    US-flag vessels

    Circ.1312 is written for ships under SOLAS and the IBC Code. A US-flag vessel in domestic service takes its foam system requirements from the 46 CFR subchapter for its vessel type, its Certificate of Inspection, the system approval and the foam manufacturer. Confirm the testing requirement there rather than carrying the IMO intervals over by default.

    Getting it done in a Mid-Atlantic port

    Baltimore Marine Safety is class approved by ABS, DNV-GL, Bureau Veritas, ClassNK, Lloyd's Register and RINA, and our fixed foam system service includes foam concentrate sample analysis along with proportioner testing, foam maker inspection and monitor and nozzle checks. We can do the sampling and the hardware checks in the same visit, which is usually the simplest way to keep the foam records and the system records in step. If the vessel also carries fixed CO2, our Baltimore Port State Control fixed CO2 guide covers that side of the same inspection.

    We work on vessels in Maryland, Pennsylvania, Delaware, New Jersey, New York and Virginia. If your foam test is coming due, or you are not sure when the concentrate came aboard, send us your vessel details and the product name from the drum or tank label.

    Note: This article summarizes IMO guidelines and SOLAS amendments for general information. Requirements depend on flag, class, vessel type, route and the equipment fitted. Always follow your flag administration, class society, the USCG and the foam manufacturer.

    References

    Frequently Asked Questions

    Ready to Ensure Your Vessel's Safety?

    Contact Baltimore Marine Safety today for professional fire protection and life safety inspections. We serve vessels in Baltimore, Philadelphia, Delaware, New Jersey, New York, and Virginia.